March 25, 1994 TO: ALL HOLDERS OF OPERATING LICENSES OR CONSTRUCTION PERMITS
FOR NUCLEAR POWER REACTORS SUBJECT: FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR
FIRE BARRIER SYSTEMS USED TO SEPARATE REDUNDANT SAFE SHUTDOWN TRAINS WITHIN THE
SAME FIRE AREA (SUPPLEMENT 1 TO GENERIC LETTER 86-10, "IMPLEMENTATION OF FIRE
PROTECTION REQUIREMENTS") PURPOSE The U.S. Nuclear Regulatory Commission (NRC)
is issuing Supplement 1 to Generic Letter (GL) 86-10, "Implementation of Fire
Protection Requirements," April 24, 1986, to disseminate the review guidance contained
in Enclosure 1, "Fire Endurance Test Acceptance Criteria for Fire Barriers Used
to Separate Redundant Safe Shutdown Trains Within the Same Fire Area." This guidance
will be used by the staff to review and evaluate the adequacy of fire endurance
tests and fire barrier systems proposed by licensees or applicants in the future
to satisfy existing NRC fire protection rules and regulations. This guidance refines
and clarifies the fire barrier testing acceptance criteria specified by GL 86-10,
for application in that specific (future review) context. BACKGROUND On April
24, 1986, the NRC issued GL 86-10 in order to give the industry additional guidance
on implementing NRC fire protection requirements. The guidance in GL 86-10 did
not change the requirement to separate one safe shutdown train from its redundant
train with either a 1-hour or a 3-hour fire rated barrier. In Enclosure 2 to GL
86-10, the NRC staff responded to industry questions. Question 3.2.1 of the enclosure
provided the staff position on fire endurance test acceptance criteria for fire
barrier cable tray wraps. In its response, the staff stated that Chapter 7, "Tests
of Nonbearing Walls and Partitions," of National Fire Protection Association (NFPA)
Standard 251, "Standard Methods of Fire Tests of Building Construction," was applicable
to cable-tray fire wraps. On July 30, 1991, the NRC established a special review
team to identify and evaluate technical issues related to the Thermo-Lag 330-1
fire barrier system. On August 6, 1991, the NRC issued Information Notice (IN)
91-47, "Failure of Thermo-Lag Fire Barrier Material to Pass Fire Endurance Test."
This IN gave licensees information on the fire endurance test performed by Gulf
States Utilities Company on a Thermo-Lag 330-1 fire barrier installed on a wide
aluminum cable tray and the associated fire test failure. On December 6, 1991,
the NRC issued IN 91-79, "Deficiencies in the Procedures for Installing Thermo-Lag
Fire Barrier Material," which gave information on deficiencies in procedures that
the Thermo-Lag vendor (Thermal Science, Incorporated) provided for constructing
Thermo-Lag 330-1 fire barriers. In 9403240197response to concerns about the indeterminate
qualifications of Thermo-Lag 330-1 fire barriers, on June 23, 1992, the NRC issued
IN 92-46, "Thermo-Lag Fire Barrier Material Special Review Team Findings, Current
Fire Endurance Tests, and Ampacity Calculation Errors." The staff found the following
problems with Thermo-Lag 330-1 fire barriers: incomplete or indeterminate fire
test results, questionable ampacity derating test results and a wide range of
documented ampacity derating factors, some barrier installations that were not
constructed in accordance with vendor-recommended installation procedures, incomplete
installation procedures, and as-built fire barrier configurations that may not
have been qualified by valid fire endurance tests or evaluated in accordance with
the guidance of GL 86-10. After reviewing INs 91-47 and 91-79, Texas Utilities
(TU) Electric Company initiated a fire endurance test program to qualify the Thermo-Lag
raceway fire barrier systems for Comanche Peak Steam Electric Station. Under this
program, TU Electric performed an initial fire barrier test series during the
weeks of June 15 and 22, and August 19, 1992. Notwithstanding the fire test acceptance
criteria guidance specified in GL 86-10, TU Electric followed the guidance of
American Nuclear Insurers (ANI) as specified in ANI Information Bulletin 5(79),
"ANI/MAERP Standard Fire Endurance Test Method to Qualify a Protective Envelope
for Class 1E Electrical Circuits," July 1979. As a result of NRC interaction with
TU Electric regarding its test program, the NRC concluded that there was uncertainty
on the part of licensees as to whether or not the ANI test method established
a level of fire barrier performance equivalent to that established by the GL 86-10
acceptance criteria. In addition, the NRC staff recognized that the 1-hour and
3-hour raceway fire barrier systems are unique and that additional guidance on
the proper implementation of the GL 86-10 acceptance criteria would be useful.
AREAS OF CONCERN The experiences with Thermo-Lag fire barrier systems at TU Electric
recounted above raised the following general concerns: (1) The fire endurance
test acceptance criteria used by other fire barrier vendors, applicants, and licensees
may not meet the acceptance criteria of GL 86-10, and may not fully demonstrate
the fire barrier performance intended. (2) Certain past cable functionality testing
(i.e., circuit integrity monitoring) may not fully demonstrate the capability
of protected circuits to function during and after a postulated fire. FIRE ENDURANCE
CAPABILITY NRC Qualification Requirements and Guidance for Fire Barriers Section
50.48 of 10 CFR requires that each operating nuclear power plant have a fire protection
plan that satisfies General Design Criterion (GDC) 3. GDC 3 requires that structures,
systems, and components important to safety be designed and located to minimize,
in a manner consistent with other safety requirements, the probability and effects
of fires. Fire protection features required to satisfy GDC 3 include features
to ensure that one train of those systems necessary to achieve and maintain shutdown
conditions be maintained free of fire damage. One means of complying with this
requirement is to separate one safe shutdown train from its redundant train with
a fire-rated barrier. The level of fire resistance required of the barrier, 1-hour
or 3-hours, depends on the other fire protection features in the fire area. The
NRC issued guidance on acceptable methods of satisfying the regulatory requirements
of GDC 3 in Branch Technical Position (BTP) Auxiliary and Power Conversion Systems
Branch (APCSB) 9.5-1, "Guidelines for Fire Protection for Nuclear Power Plants;"
Appendix A to BTP APCSB 9.5-1; BTP Chemical Engineering Branch (CMEB) 9.5-1, "Fire
Protection for Nuclear Power Plants;" and GL 86-10. In the BTPs and in GL 86-10,
the staff stated that the fire resistance ratings of fire barriers should be established
in accordance with NFPA Standard 251, "Standard Methods of Fire Tests of Building
Construction and Materials," by subjecting a test specimen that represents the
materials, workmanship, method of assembly, dimensions, and configuration for
which a fire rating is desired to a "standard fire exposure." Some licensees have
used the acceptance criteria of ANI Bulletin No. 5(79), to evaluate the performance
of their fire barrier systems. The ANI test methodology, which ANI issued for
insurance purposes only, requires that cables within the fire barrier test specimen
be monitored for circuit integrity while the test specimen is subjected to a test
fire that follows the standard time-temperature curve specified in American Society
of Testing and Materials (ASTM) Standard E-119, "Standard Methods of Fire Tests
of Building Construction and Materials," and to a hose stream test. Under this
criterion, the fire barrier system is evaluated by monitoring the capability of
the cables inside the fire barrier to pass a low voltage circuit integrity test.
During the fire and hose stream tests, if cable circuit integrity is maintained,
the tests are considered successful. The ANI test methodology does not specify
the following GL 86-10 acceptance criteria: (1) The fire barrier design has withstood
the fire endurance test without the passage of flame or the ignition of cotton
waste on the unexposed side for a period of time equivalent to the fire-resistance
rating required of the barrier. (2) Analysis of temperature levels recorded on
the unexposed side of the fire barrier demonstrates that the maximum temperature
rise does not exceed 139 øC [250 øF] above ambient temperature. (3) The fire barrier
remains intact and does not allow water to be projected beyond the unexposed surface
during the hose stream test. Enclosure 1, "Interpretations of Appendix R," to
GL 86-10, provided additional guidance with respect to the term "free of fire
damage" as used in Appendix R. Interpretation 3, "Fire Damage," stated: "In promulgating
Appendix R, the Commission has provided methods acceptable for assuring that necessary
structures, systems, and components are free from fire damage (see Section III.G.2a,
b, and c), that is, the structure, system or component under consideration is
capable of performing its intended function during and after the postulated fire,
as needed." The review guidance provided in Enclosure 1 (1) clarifies the applicability
of the test acceptance criteria stated in GL 86-10 to raceway fire barrier systems,
(2) specifies a set of fire endurance test acceptance criteria which are acceptable
for demonstrating that fire barrier systems can perform the required fire-resistive
function and maintain the protected safe shutdown train free of fire damage, (3)
specifies acceptable options for hose stream testing, and (4) specifies acceptable
criteria for functionality testing of cables when a deviation is necessary, such
as when the fire barrier temperature rise criteria are exceeded or the test specimen
cables sustain visible damage. The test methods and acceptance criteria specified
in Enclosure 1 are acceptable for determining the adequacy of fire barrier systems
proposed by licensees or applicants in the future to satisfy NRC fire protection
rules and regulations. Applicants or licensees may propose alternative test methods
and acceptance criteria to demonstrate an equivalent level of protection; the
staff will review such proposals on a case-by-case basis. Enclosure 2 is a summary
comparison of this review guidance against the GL 86-10 acceptance criteria. Evaluation
and Application of Fire Endurance and Functionality Test Results The fire endurance
qualification test is successful for a raceway fire barrier if the following conditions
are satisfied (see Enclosure 3, "Fire Barrier Testing Acceptance Criteria/Logic
Diagram"): (1) The average internal temperature of the fire barrier system, as
measured on the exterior surface of the raceway or component, did not rise more
than 139 øC [250 øF] above its initial temperature; and (2) When cables or components
are included in the test specimen, a visual inspection of the protected cables
or components revealed no signs of degraded conditions from the thermal effects
of the fire exposure; and (3) The fire barrier system remained intact during the
fire exposure and hose stream tests without developing any openings through which
the protected component, raceway, or cables are visible. For raceway fire barrier
systems, the staff adopted the hose stream testing methodology specified in NUREG-0800,
"Standard Review Plan (SRP) for the Review of Safety Analysis Reports for Nuclear
Power Plants," Section 9.5.1, "Guidelines for Fire Protection for Nuclear Power
Plants," Revision 2, July 1981, Position 5.a. This SRP position established the
acceptability of using the fog nozzle method for hose stream testing of fire barrier
penetration seals. The fog nozzle hose stream test method is an acceptable option
for tests of the entire raceway fire barrier system under the new staff position.
Licensees that propose to use fire endurance test results that deviate from the
acceptance criteria as the bases for qualifying and installing fire barrier configurations,
should request a deviation from the acceptance criteria based on a engineering
evaluation acceptable to the staff, such as demonstrating cable functionality.
For those licensees required to comply with Section III.G to Appendix R, the engineering
evaluation justifying the deviating conditions should be submitted with the exemption
request. The review guidance provided in Enclosure 1 provides specific guidance
for demonstrating cable functionality, including subjecting the cables to Megger
and high-potential tests. The results of these tests can be used to determine
the insulation-resistance characteristics of the thermally damaged cable and to
determine if the cable insulation would have been sufficient to maintain circuit
functionality during and after the fire exposure. IMPLEMENTATION This section
describes how the NRC plans to use the review guidance contained in Enclosure
1. After this supplement to GL 86-10 is issued, except in those cases in which
an applicant or licensee has proposed an acceptable alternative fire endurance
test method and acceptance criteria that demonstrates an equivalent level of fire
protection, the NRC will use the methods and the criteria specified in the enclosed
review guidance to (1) evaluate fire endurance testing programs proposed by licensees
or applicants in the future for demonstrating compliance with pertinent NRC fire
protection rules and regulations and (2) review the adequacy of the fire barrier
systems proposed in the future by applicants or licensees. ACTIONS REQUESTED None.
REPORTING REQUIREMENTS None. BACKFIT DISCUSSION The guidance transmitted by this
generic letter supplement will be used by the staff for review and evaluation
of the adequacy of fire barrier systems and fire endurance tests that may be proposed
in the future to satisfy NRC fire protection rules and regulations. This guidance
refines and clarifies the guidance specified in Generic Letter 86-10 for application
in that future review context; specifically it (1) clarifies the applicability
of the test acceptance criteria stated in GL 86-10 to raceway fire barrier systems,
(2) specifies a set of fire endurance test acceptance criteria which are acceptable
for demonstrating that fire barrier systems can serve the required fire-resistive
function and maintain the protected safe shutdown train free of fire damage, (3)
contains acceptable options for hose stream testing, and (4) specifies acceptable
criteria for functionality testing of cables when a deviation would be necessary,
such as if the fire barrier temperature rise criteria are exceeded or the cable
sustains visible damage. No generic or plant-specific backfitting is intended
or approved at this time in connection with issuance of this review guidance.
The staff may consider the need for further generic action in that regard, if
the industry guidance currently under development for addressing the pertinent
fire protection issues is substantively inconsistent with this staff review guidance;
but such action would be separately justified in accordance with the criteria
of 10 CFR 50.109 and existing NRC backfit procedures. Similarly, if plant-specific
backfits are proposed by the NRC staff consistent with this review guidance, the
proposed backfits would be justified on a case-by-case basis in accordance with
the criteria of 10 CFR 50.109 and existing NRC backfit procedures. If you have
any questions about this matter, please contact one of the contacts listed below
or the appropriate Office of Nuclear Reactor Regulation project manager. Sincerely,
/s/'d by LAReyes Luis A. Reyes Acting Associate Director for Projects Office of
Nuclear Reactor Regulation Enclosures: 1. NRC Staff Review Guidance and Fire Endurance
Test Acceptance Criteria for Fire Barrier Systems Used To Separate Redundant Safe
Shutdown Trains Within the Same Fire Area. 2. Comparison of Staff Position on
Fire Endurance Test Acceptance Criteria for Fire Barrier Systems Used To Separate
Redundant Safe Shutdown Trains Within the Same Fire Area to the Acceptance Criteria
of GL 86-10. 3. NRC Fire Testing Acceptance Criteria Logic Diagram. Technical
contact: Patrick M. Madden, NRR (301) 504-2854 Lead Project Manager: Marsha K.
Gamberoni, NRR (301) 504-3024 FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR FIRE
BARRIER SYSTEMS USED TO SEPARATE REDUNDANT SAFE SHUTDOWN TRAINS WITHIN THE SAME
FIRE AREA I. BACKGROUND In 1975, the Browns Ferry Nuclear power plant experienced
a serious electrical cable tray fire. This fire had a significant impact on operator
response to the event from a safety perspective. The fire caused spurious instrumentation
indications and affected the control of several safety systems. As a result of
this fire, the NRC issued the following fire protection guidelines and regulations
concerning fire protection programs at nuclear power plants: May 1, 1976 Branch
Technical Position (APCSB) 9.5-1, "Fire Protection Program." February 24, 1977
Appendix A to Branch Technical Position APCSB 9.5-1, "Guidelines for Fire Protection
for Nuclear Power Plants Docketed Prior to July 1, 1976." February 19, 1981 10
CFR 50.48, "Fire Protection." February 19, 1981 Appendix R to 10 CFR Part 50,
"Fire Protection Program for Nuclear Power Facilities Operating Prior to January
1979." July 1981 NUREG-0800, Standard Review Plan (SRP), 9.5.1, "Fire Protection
for Nuclear Power Plants." In addition to the above fire protection guidance and
regulations, the NRC, in an effort to clarify its fire protection requirements
to the industry, issued Generic Letter (GL) 81-12, "Fire Protection Rule (45 FR
76602, November 19, 1980)," February 20, 1981; GL 83-33, "NRC Position on Certain
Requirements of Appendix R to 10 CFR 50," October 19, 1983; and GL 86-10, "Implementation
of Fire Protection Requirements," April 24, 1986. GL 86-10, which took precedence
over previous staff guidance, provided staff interpretations to Appendix R and
answers to industry questions regarding the implementation of Appendix R. The
NRC, in an effort to give the licensees flexibility to make changes to its plant
specific fire protection program, issued GL 88-12, "Removal of Fire Protection
Requirements From Technical Specifications," August 2, 1988. Through the implementation
and the adoption of a standard license condition, a licensee can make changes
which do not adversely affect the ability to achieve and maintain post-fire safe
shutdown to its fire protection program in accordance with 10 CFR 50.59. The aforementioned
NRC documents provided NRC staff guidance concerning fire barriers separating
plant fire areas, including the fire resistance (endurance) ratings for the barriers
and the qualification tests that establish their fire resistance ratings. In addition,
the documents provided guidance on combustibility of structural materials and
tests for demonstrating low flame spread properties. The following sections of
this document provide the objective for providing safe shutdown related fire barriers
in nuclear power plants, definition of fire protection terms related to fire barriers,
and the NRC fire endurance test acceptance criteria for fire barriers used to
separate safe shutdown functions within the same fire area. II. OBJECTIVE OF FIRE
BARRIERS USED TO SEPARATE SAFE SHUTDOWN FUNCTIONS WITHIN THE SAME FIRE AREA Fire
rated barriers are used in nuclear power plants to provide fire area separation
between redundant safety-related components and safe shutdown functions. They
provide fire resistance protection, as required by Appendix R, to one safe shutdown
train in those fire areas which contain both trains. The objective of the safe
shutdown related Appendix R fire barrier is to ensure that a safe shutdown train
is conservatively protected from fire-related thermal damage. The necessity for
these fire barriers has been verified by multiple probabilistic risk assessments
(PRAs). These PRAs indicated that, even with fire barriers installed, fires are
a major contributor to core melt probabilities. It is the position of the NRC
that fire endurance ratings of building construction and materials are demonstrated
by testing fire barrier assemblies in accordance with the provisions of the applicable
sections of NFPA 251, "Standard Methods of Fire Tests of Building Construction
and Materials," and ASTM E-119, "Fire Test of Building Construction and Materials."
Assemblies that pass specified acceptance criteria (e.g., standard time-temperature
fire endurance exposure, unexposed side temperature rise, and hose stream impingement)
are considered to have a specific fire resistance rating. Enclosure 1 to GL 86-10,
"Interpretations of Appendix R," provided additional guidance with respect to
the term "free from fire damage." Interpretation 3, "Fire Damage," states, "In
promulgating Appendix R, the Commission has provided methods acceptable for assuring
that necessary structures, systems, and components are free from fire damage (see
Section III.G.2a, b, and c), that is, the structure, system or component under
consideration is capable of performing its intended function during and after
the postulated fire, as needed." GL 86-10, Response 3.2.1, also stated that, "The
resulting 325 øF cold side temperature criterion is used for cable tray wraps
because they perform a fire barrier function to preserve the cables free from
fire damage. It is clear that cable that begins to degrade at 450 øF is free from
fire damage at 325 øF." (Emphasis added.) In addition, the staff response stated
that, "for newly identified conduit and cable trays requiring such wrapping new
materials which meet the 325 øF criterion should be used, or justification should
be provided for the use of material which does not meet the 325 øF criterion.
This may be based on an analysis demonstrating that the maximum recorded temperature
is sufficiently below the cable insulation ignition temperature." (Emphasis added.)
The basic premise of the NRC fire resistance criteria is that fire barriers which
do not exceed 163 øC [325 øF] cold side temperature and pass the hose stream test
provide adequate assurance that the shutdown capability is protected without further
analyses. If the temperature criteria is exceeded, sufficient additional information
is needed to perform an engineering evaluation to demonstrate that the shutdown
capability is protected. III. DEFINITIONS In order to support the understanding
of the technical terms used throughout this document, the following definitions
are provided. Combustible Material - Material that does not meet the definition
of non- combustible. Fire Barrier - Those components of construction (walls, floors
and their supports), including beams, joists, columns, penetration seals or closures,
fire doors, and fire dampers that are rated by approving laboratories in hours
of resistance to fire and are used to prevent the spread of fire. Fire Resistance
Rating - The time that materials of a test assembly have withstood a standard
ASTM E-119 fire exposure and have successfully met the established test acceptance
criteria (fire barrier test acceptance criteria refer to Sections IV, V, and VI).
Noncombustible Material - (a) Material which, in the form in which it is used
and under the conditions anticipated, will not ignite, burn, support combustion,
or release flammable vapors when subjected to fire or heat; (b) Material having
a structural base of noncombustible material, with a surfacing not over 1/8-inch
thick that has a flame spread rating of not higher than 50 when measured in accordance
with ASTM E-84, "Surface Burning Characteristics of Building Materials." (There
is an exception to this definition as defined by BTP Appendix A, Position D.1.d.
This position allows the use of combustible interior finishes when listed by a
nationally recognized test laboratory, such as Factory Mutual or Underwriters
Laboratories, Incorporated, for a flame spread, smoke and fuel contribution of
25 or less in its use configuration.) Raceway - Cable trays, conduits, junction
boxes, and other components used to support and route cables from circuit termination
to circuit termination. Raceway Fire Barrier - Nonload bearing partition type
envelope system installed around electrical components and cabling that are rated
by test laboratories in hours of fire resistance and are used to maintain safe
shutdown functions free of fire damage. IV. FIRE ENDURANCE TEST ACCEPTANCE CRITERIA
FOR FIRE BARRIER WALLS, FLOORS, CEILINGS, AND FREE STANDING EQUIPMENT ENCLOSURES
USED TO SEPARATE SAFE SHUTDOWN FUNCTIONS WITHIN THE SAME FIRE AREA To demonstrate
the adequacy of fire barrier walls, floors, ceilings, and enclosures, barrier
designs should be verified by fire endurance testing. NRC fire protection guidance
refers to the guidance of NFPA 251 and ASTM E-119 as acceptable test methods for
demonstrating fire endurance performance. The fire endurance test acceptance criteria
for the subject fire barriers are: The fire barrier design has withstood the fire
endurance test without the passage of flame or the ignition of cotton waste on
the unexposed side for a period of time equivalent to the fire resistance rating
required of the barrier; The temperature levels recorded on the unexposed side
of the fire barrier are analyzed and demonstrable that the maximum temperature
does not exceed 139 øC [250 øF] above ambient; and The fire barrier remains intact
and does not allow projection of water beyond the unexposed surface during the
hose stream test. (For acceptable hose stream test methods and time of application
- See Section VII.) If the above criteria are met for fire barrier walls, floors,
ceilings, and free standing equipment enclosures separating safe shutdown functions
within the same fire area, the barrier is acceptable. NRC fire protection guidance
also ensures that door and ventilation openings and penetrations are properly
protected. The guidance requires that these openings be protected with fire doors
and fire dampers which have been fire tested and listed by a nationally recognized
test laboratory (e.g., Factory Mutual or Underwriters Laboratories, Incorporated).
In addition, the construction and installation techniques for door and ventilation
openings and other penetrations through these fire barriers should be qualified
by fire endurance tests. The guidance of NFPA 251 and ASTM E-119 should be consulted
with regard to construction, materials, workmanship, and details such as dimensions
of parts, and the size of the specimen(s) to be tested. In addition, NFPA 251
and ASTM E-119 should be consulted with regard to the placement of thermocouples
on the specimen. V. FIRE ENDURANCE TEST ACCEPTANCE CRITERIA FOR ELECTRICAL RACEWAY
AND COMPONENT FIRE BARRIER SYSTEMS FOR SEPARATING SAFE SHUTDOWN FUNCTIONS WITHIN
THE SAME FIRE AREA The NRC provided guidance in Appendix A to Branch Technical
Position 9.5-1, Position D.3.(d), for cable tray fire barriers. This fire protection
guidance states that the design of fire barriers for horizontal and vertical cable
trays should, as a minimum, meet the requirements of ASTM E-119, "Fire Test of
Building Construction and Materials," including hose stream test. On November
19, 1980, the NRC issued Appendix R to 10 CFR Part 50. The technical basis for
Section III.M, "Fire Barrier Penetration Seal Qualification," states that "Fire
barriers are `rated' for fire resistance by being exposed to a `standard test
fire.' This standard test fire is defined by the American Society of Testing and
Materials in ASTM E-119." In addition, this technical basis stated that "[i]f
specific plant conditions preclude the installation of a 3-hour fire barrier to
separate the redundant trains, a 1-hour fire barrier and automatic fire suppression
and detection system for each redundant train will be considered the equivalent
of a 3-hour barrier." Appendix R to 10 CFR Part 50, Section III.G, "Fire protection
of safe shutdown capability," provides what the NRC views as equivalent means
for ensuring that one safe shutdown train remains free of fire damage. In 1984
Appendix R workshops held with industry, and later in GL 86-10, the staff provided
guidance related to fire barrier designs for raceways. In Enclosure 2, "Question
and Answers," to this GL, Question 3.2.1., "Acceptance Criteria," the staff provided
guidance on the cold side temperature for fire barrier cable tray wraps. In response
to this question the staff stated that the acceptance criteria contained in Chapter
7 of NFPA 251, "Standard Methods of Fire Tests of Building Construction and Materials,"
pertaining to non- bearing fire barriers was applicable to cable tray fire barrier
wraps. Chapter 5 of NFPA 251 explains the conduct of the fire test. The following
is the NFPA 251 acceptance criteria: - The wall or partition withstood the fire
endurance test without the passage of flame or gases hot enough to ignite cotton
waste, for a period equal to that for which classification is desired; - The wall
or partition withstood the fire and hose stream tests specified in Chapter 5,
without the passage of flame, gases hot enough to ignite cotton waste, or the
hose stream. The assembly failed the hose stream test if an opening develops that
permits the projection of water from the stream beyond the unexposed surface during
the hose stream test; and - Transmission of heat through the wall or partition
during the fire endurance test did not raise the temperature on the unexposed
surfaces more than 139 øC [250 øF] above their initial temperatures. The staff
considers the fire endurance qualification test for fire barrier materials applied
directly to a raceway or component to be successful if the following conditions
are met: - The average unexposed side temperature of the fire barrier system,
as measured on the exterior surface of the raceway or component, did not exceed
139 øC [250 øF] above its initial temperature; and (Staff Guidance: NFPA 251 and
ASTM E-119 allow this temperature to be determined by averaging thermocouple temperature
readings. For the purposes of this criterion, thermocouple averaging can be used
provided similar series of thermocouples (e.g., cable tray side rail) are averaged
together to determine temperature performance of the raceway fire barrier system.
In addition, conditions of acceptance are placed on the temperatures measured
by a single thermocouple. If any single thermocouple exceeds 30 percent of the
maximum allowable temperature rise (i.e., 139 øC + 42 øC = 181 øF [250 øF + 75
øF = 325 øF]), the test exceeded the temperature criteria limit.) - Irrespective
of the unexposed side temperature rise during the fire test, if cables or components
are included in the fire barrier test specimen, a visual inspection should be
performed. Cables should not show signs of degraded conditions resulting from
the thermal affects of the fire exposure; and (Staff Guidance: For those cases
where signs of thermal degradation are present, the fire barrier did not perform
its intended fire-resistive function. For those barriers which are not capable
of performing their intended function, a deviation based on demonstrating that
the functionality of thermally degraded cables or component was maintained and
that the cables or component would have adequately performed their intended function
during and after a postulated fire exposure may be granted. The attachment to
this position provides a methodology for demonstrating the functionality of cables
during and after a fire test exposure. The purpose of the functionality tests
is to justify observed deviations in fire barrier performance. For those fire
barrier test specimens that are tested without cables, an engineering analysis
justifying internal fire barrier temperature conditions greater than allowed can
be based on a comparison of the fire barrier internal temperature profile measured
during the fire endurance test to existing cable specific performance data, such
as environmental qualification (EQ) tests.) - The cable tray, raceway, or component
fire barrier system remained intact during the fire exposure and water hose stream
test without developing any openings through which the cable tray, raceway, or
component (e.g., cables) is visible. Section VII identifies acceptable hose stream
test methods. The test specimen should be representative of the construction for
which the fire rating is desired as to materials, workmanship, and details such
as dimensions of parts, and should be built under representative conditions. Raceway
fire barrier systems being subjected to qualification fire endurance tests should
be representative of the end use. For example, if it is intended to install a
cable tray fire barrier system in the plant without protecting the cable tray
supports, then the test program should duplicate these field conditions. In addition,
the fire test program should encompass or bound raceway sizes and the various
configurations for those fire barrier systems installed in the plant. It should
be noted that several test specimens will be required in order to qualify various
sizes of horizontal and vertical runs of cable trays and conduits, junction boxes
and pull boxes, etc. The cable tray or raceway design used for the tests should
be constructed with materials and configurations representative of in plant conditions
(e.g., the mass associated with typical steel conduits and cable trays, representative
internal and external penetration seals). If cables are included in the raceway
fire barrier test specimen, these cables should be representative of the installed
plant-specific cables. Measuring cable temperatures is not a reliable means for
determining excessive temperature conditions which may occur at any point along
the length of the cable during the fire test. In lieu of measuring the unexposed
surface temperature of the fire barrier test specimen, methods which will measure
the surface temperature of the raceway (e.g., exterior of the conduit, side rails
of cable trays, bottom and top of cable tray surfaces, junction box external surfaces)
can be considered as equivalent if the raceway components used to construct the
fire test specimen represent plant specific components and configurations. The
metal surfaces of the raceway, under fire test conditions, exhibit good thermal
conductivity properties. Temperatures measured on these surfaces provide a indication
of the actual temperature rise within the fire barrier system. In 1979, American
Nuclear Insurers (ANI) issued a fire endurance test method for raceway fire barrier
systems for insurance purposes. This method, "Fire Endurance Protective Envelope
Systems for Class 1E Electrical Circuits," specified that cable temperatures be
monitored by thermocouples. Industry considers this the proper location for determining
the temperature rise within the raceway fire barrier system. Since cable jackets
have a low thermal conductivity, the actual local temperatures of the cable jackets
indications of barrier failure and internal fire barrier temperature rise conditions
during the fire exposure are masked. Monitoring cable temperatures can give indications
of low internal fire barrier temperature conditions during the fire endurance
test. Using this temperature monitoring approach, cable damage can occur without
indication of excessive temperatures on the cables. This, linked with no loss
of circuit integrity, would give indications of a successful test. The staff considers
monitoring the cable temperature as the primary means of determining cable tray
or raceway fire barrier performance to be nonconservative. Therefore, the staff
has incorporated the provision for a post-fire visual inspection of cables that
are installed in fire barrier test specimens. As discussed above, temperatures
monitored on the exterior surface of the raceway provide a more representative
indication of fire barrier performance. Fire endurance tests of raceway fire barrier
systems should be without cables. This method is preferred because by excluding
cables from the test specimen it eliminates bias in the test results created by
the thermal mass of the cables. Without this thermal mass, the internal temperature
conditions measured by the test specimen thermocouples during the fire exposure
will provide a more accurate determination of fire barrier thermal performance.
Thermocouple Placement - Test Specimens Containing Cables The following are acceptable
placements of thermocouples for determining the thermal performance of raceway
or cable tray fire barrier systems that contain cables during the fire exposure:
Conduits - The temperature rise on the unexposed surface of a fire barrier system
installed on a conduit should be measured by placing the thermocouples every 152
mm [6 inches] on the exterior conduit surface underneath the fire barrier material.
The thermocouples should be attached to the exterior conduit surface located opposite
the test deck and closest to the furnace fire source. Thermocouples should also
be placed immediately adjacent to all structural members, supports, and barrier
penetrations. Cable Trays - The temperature rise on the unexposed surface of a
fire barrier system installed on a cable tray should be measured by placing the
thermocouples on the exterior surface of the tray side rails between the cable
tray side rail and the fire barrier material. In addition to placing thermocouples
on the side rails, thermocouples should be attached to two AWG 8 stranded bare
copper conductors. The first copper conductor should be installed on the bottom
of the cable tray rungs along the entire length and down the longitudinal center
of the cable tray run. The second conductor should be installed along the outer
top surface of the cables closest to the top and towards the center of the fire
barrier. The bare copper wire is more responsive than cable jackets to temperature
rise within the fire barrier enclosure. The temperature changes measured along
the bare copper conductors provide indication of joint failure or material burn
through conditions. Thermocouples should be placed every 152 mm [6 inches] down
the longitudinal center along the outside surface of the cable tray side rails
and along the bare copper conductors. Thermocouples should also be placed immediately
adjacent to all structural members, supports, and barrier penetrations. Junction
Boxes (JB) - The temperature rise on the unexposed surface of a fire barrier system
installed on junction boxes should be measured by placing thermocouples on either
the inside or the outside of each JB surface. Each JB surface or face should have
a minimum of one thermocouple, located at its geometric center. In addition, one
thermocouple should be installed for every one square foot of JB surface area.
These thermocouples should be located at the geometric centers of the one square
foot areas. At least one thermocouple should also be placed within 25 mm [1 inch]
of each penetration connector/interface. Airdrops - The internal airdrop temperatures
should be measured by thermocouples placed every 305 mm [12 inches] on the cables
routed within the air drop and by a stranded AWG 8 bare copper conductor routed
inside and along the entire length of the airdrop system with thermocouples installed
every 152 mm [6 inches] along the length of the copper conductor. The copper conductor
should be in close proximity with the unexposed surface of the fire barrier material.
Thermocouples should also be placed immediately adjacent to all supports and barrier
penetrations. With the exception of airdrops, the installation of thermocouples
on cables is optional and is left to the discretion of the licensee, test sponsor,
or test laboratory. Cable thermocouples are to be used for engineering purposes
only. Cable thermocouples alone are not acceptable for the demonstration of fire
barrier performance. However, cable thermocouples may support fire barrier deviation
conditions. Temperature conditions on the unexposed surface of the fire barrier
material during the fire test will be determined by averaging the temperatures
measured by the thermocouples. In determining these cable tray or raceway temperature
conditions, the thermocouples measuring similar fire barrier areas of performance
should be averaged together and the basis of acceptance will be based on the individual
averages. The following method of averaging should be followed: Conduits - The
thermocouples applied to the outside metal surface of the conduit should be averaged
together. Cable Trays - The thermocouples on each cable tray side rail should
be averaged separately. For example, thermocouples placed on one side rail will
be averaged separately from the other side rail. In addition, the temperature
conditions measured by thermocouples on the two bare copper conductors should
be averaged separately. Junction Boxes - For small JBs which have only one thermocouple
placed on each JB surface, the individual JB surface thermocouples should be averaged
together. For larger JBs which have more that one thermocouple placed on each
JB surface, the thermocouples on the individual JB surfaces should be averaged
together. Airdrops - The thermocouples placed on the outer cable(s) routed in
the airdrop fire barrier should be averaged together. The averages of any thermocouple
group during the fire test should not exceed 139 øC [250 øF] above the unexposed
side temperature within the fire barrier test specimen at the onset of the fire
endurance test. In addition, the temperature of each individual thermocouple will
be evaluated. Individual thermocouple conditions should not exceed the 139 øC
[250 øF] temperature rise by more than 30 percent. Thermocouple Placement - Test
Specimens Without Cables The following are acceptable thermocouple placements
for determining the thermal performance of raceway or cable tray fire barrier
systems that do not contain cables: Conduits - The temperature rise of the unexposed
surface of a fire barrier system installed on a conduit should be measured by
placing thermocouples every 152 mm [6 inches] on the exterior conduit surface
between the conduit and the unexposed surface of the fire barrier material. These
thermocouples should be attached to the exterior conduit surface opposite of the
test deck and closest to the furnace fire source. The internal raceway temperatures
should be measured by a stranded AWG 8 bare copper conductor routed through the
entire length of the conduit system with thermocouples installed every 152 mm
[6 inches] along the length of the copper conductor. Thermocouples should also
be placed immediately adjacent to all structural members, supports, and barrier
penetrations. Cable Trays - The temperature rise on the unexposed surface of a
fire barrier system installed on a cable tray should be measured by placing thermocouples
every 152 mm [6 inches] on the exterior surface of each tray side rails between
the side rail and the fire barrier material. Internal raceway temperatures should
be measured by a stranded AWG 8 bare copper conductor routed on the top of the
cable tray rungs along the entire length and down the longitudinal center of the
cable tray run with thermocouples installed every 152 mm [6 inches] along the
length of the copper conductor. Thermocouples should be placed immediately adjacent
to all structural members, supports, and barrier penetrations. Junction Boxes
- The temperature rise on the unexposed surface of a fire barrier system installed
on junction boxes should be measured by placing thermocouples on either the inside
or the outside of each JB surface. Each JB surface or face should have a minimum
of one thermocouple, located at its geometric center. In addition, one thermocouple
should be installed for every one square foot of JB surface area. These thermocouples
should be located at the geometric centers of the one square foot areas. At least
one thermocouple should also be placed within 25 mm [1 inch] of each penetration
connector/interface. Airdrops - The internal airdrop temperatures should be measured
by a stranded AWG 8 bare copper conductor routed inside and along the entire length
of the airdrop system with thermocouples installed every 152 mm [6 inches] along
the length of the copper conductor. The copper conductor should be in close proximity
with the unexposed surface of the fire barrier material. Thermocouples should
also be placed immediately adjacent to all supports and penetrations. Temperature
conditions on the unexposed surfaces of the fire barrier material during the fire
test will be determined by averaging the temperatures measured by the thermocouples
installed in or on the raceway. In determining these temperature conditions, the
thermocouples measuring similar areas of the fire barrier should be averaged together.
Acceptance will be based on the individual averages. The following method of averaging
should be followed: Conduits - The thermocouples applied to the outside metal
surface of the conduit should averaged together. Cable Trays - The thermocouples
on each cable tray side rail should be averaged separately. For example, thermocouple
placed on one side rail will be averaged separately from the other side rail.
In addition, the temperature conditions measured by thermocouples on the bare
copper conductor should be averaged separately from the side rails. Junction Boxes
- For JBs that have only one thermocouple on each JB surface, the individual JB
surface thermocouples should be averaged together. For JBs that have more that
one thermocouple on each JB surface, the thermocouples on the individual JB surfaces
should be averaged together. Airdrops - The thermocouples placed on the copper
conductor within the airdrop fire barrier should be averaged together. The average
of any thermocouple group should not exceed 139 øC [250 øF] above the unexposed
side temperature within the fire barrier test specimen at the onset of the fire
endurance test. In addition, the temperature of each individual thermocouple will
be evaluated. Individual thermocouple conditions should not exceed the 139 øC
[250 øF] temperature rise by more than 30 percent. If a fire barrier test specimen
without cables does not meet the average or maximum single point temperature criteria,
then the internal raceway temperature profile as measured by the instrumented
bare copper conductors during the fire exposure can be used to assess cable functionality
through air oven tests of plant specific cable types and construction. VI. HOSE
STREAM TESTS NFPA 251 and ASTM E-119 allow flexibility in hose stream testing.
The standards allow the hose stream test to be performed on a duplicate test specimen
subjected to a fire endurance test for a period equal to one-half of that indicated
as the fire resistance rating, but not for more than 1 hour (e.g., 30 minute fire
exposure to qualify a 1-hour fire rated barrier). For safe shutdown related fire
barrier systems referenced in Section IV and duplicate electrical cable tray or
raceway and component fire barrier test specimens that have been exposed to the
«-duration test fire exposure, the staff finds the hose stream application specified
by the NFPA 251 acceptable. NFPA 251 requires the stream of water to be delivered
through a 6.4 cm [2«- inch] hose discharging through a standard 2.9 cm [1þ-inch]
playpipe nozzle onto the test specimen after the fire exposure test. The stream
is applied with the nozzle orifice positioned 6.1 meters [20 feet] away from the
center of the test specimen at a pressure of 207 kPa [30 psi]. The application
of the stream is to all exposed parts of the specimen for a minimum duration of
1 minute for a 1-hour barrier and 2« minutes for a 3-hour barrier. As an alternate
for electrical raceway fire barrier test specimens, the application of the hose
stream test can be performed immediately after the completion of the full fire
endurance test period. If this method is used to satisfy the hose stream test
criteria, the following hose stream applications are acceptable: - The stream
applied at random to all exposed surfaces of the test specimen through a 6.4 cm
[2«-inch] national standard playpipe with a 2.9 cm [1þ-inch] orifice at a pressure
of 207 kPa [30 psi] at a distance of 6.1 meters [20 feet] from the specimen. (Duration
of the hose stream application - 1 minute for a 1-hour barrier and 2« minutes
for a 3-hour barrier); or - The stream applied at random to all exposed surfaces
of the test specimen through a 3.8 cm [1«-inch] fog nozzle set at a discharge
angle of 30 degrees with a nozzle pressure of 517 kPa [75 psi] and a minimum discharge
of 284 lpm [75 gpm] with the tip of the nozzle at a maximum of 1.5 meters [5 feet]
from the test specimen. (Duration of the hose stream application - 5 minutes for
both 1-hour and 3-hour barriers); or - The stream applied at random to all exposed
surfaces of the test specimen through 3.8 cm [1«-inch] fog nozzle set at a discharge
angle of 15 degrees with a nozzle pressure of 517 kPa [75 psi] and a minimum discharge
of 284 lpm [75 gpm] with the tip of the nozzle at a maximum of 3 meters [10 feet]
from the test specimen. (Duration of the hose stream application - 5 minutes for
both 1- hour and 3-hour barriers.) VII. FIRE BARRIER COMBUSTIBILITY The NRC's
fire protection guidelines and requirements establish the need for each nuclear
power plant to perform a plant-specific fire hazard analysis. The fire hazard
analysis should consider the potential for in-situ and transient fire hazards
and combustibles. With respect to building materials (e.g., cable insulation and
jackets, plastics, thermal insulation, fire barrier materials), the combustibility,
ease of ignition, and flame spread over the surface of a material should be considered
by the fire hazards analysis. One method of determining combustibility is by subjecting
a sample of the fire barrier material to a small scale vertical tube furnace as
described by ASTM E-136. The flashover ignition temperature of the material (as
determined by ASTM D-1929) and the flame spread characteristics of the material
(as determined by ASTM E-84) should also be evaluated. The potential heat release
of the material (as determined by ASTM D-3286 or NFPA 259), should also be factored
into the fire hazards analysis. Fire barrier materials used as radiant energy
heat shields inside containment and used to achieve a combustible free zone are
required to be noncombustible as defined in Section III. VIII. REFERENCES U.S.
Nuclear Regulatory Commission May 1, 1976 Branch Technical Position (APCSB) 9.5-1,
"Fire Protection Program." February 24, 1977 Appendix A to the Branch Technical
Position APCSB 9.5-1, "Guidelines for Fire Protection for Nuclear Power Plants
Docketed Prior to July 1, 1976." February 19, 1981 10 CFR 50.48, "Fire protection."
February 19, 1981 Appendix R to 10 CFR Part 50, "Fire Protection for Nuclear Power
Plants." February 20, 1981 Generic Letter 81-12, "Staff Position - Safe Shutdown
Capability." July 1981 NUREG - 0800, Standard Review Plan, 9.5.1, "Fire Protection
for Nuclear Power Plants." October 19, 1983 Generic Letter 83-33, "NRC Positions
on Certain Requirements of Appendix R to 10 CFR 50." April 24, 1986 Generic Letter
86-10, "Implementation of Fire Protection Requirements." American Society for
Testing and Materials ASTM E-84, "Surface Burning Characteristics of Building
Materials." ASTM E-119, "Fire Test of Building Construction and Materials." ASTM
E-136, "Behavior of Materials in a Vertical Tube Furnace at 750øC." ASTM D-1929,
"Test Method for Ignition Properties of Plastics." ASTM D-3286, "Test Method for
Gross Calorific Value of Solid Fuel by the Isothermal-Jacket Bomb Calorimeter."
American Nuclear Insurers (ANI) July 1979, ANI Information Bulletin No. 5 (79)
test criteria for "Fire Endurance Protective Envelope Systems for Class 1E Electrical
Circuits." National Fire Protection Association (NFPA) NFPA 251, "Standard Methods
of Fire Tests of Building Construction and Materials." NFPA 259, "Standard Test
Method for Potential Heat of Building Materials." ACCEPTABLE METHODS FOR DEMONSTRATING
FUNCTIONALITY OF CABLES PROTECTED BY RACEWAY FIRE BARRIER SYSTEMS DURING AND AFTER
FIRE ENDURANCE TEST EXPOSURE I. INTRODUCTION The NRC considers fire barrier systems
that meet the acceptance criteria adequate under NRC fire protection regulations.
The licensee, where the criteria are not met, should submit an engineering analysis
to the staff that clearly demonstrates the functionality of the protected cables.
This engineering analysis should consider the cable insulation type, actual voltage
and current conditions, cable function, and thermal affects on the cable and its
ability to function. This evaluation should also consider cable operating temperatures
within the fire barrier at the onset of the fire exposure. II. CABLE CIRCUIT INTEGRITY
TESTS In 1979, American Nuclear Insurers (ANI) issued a fire endurance test method
for raceway fire barrier systems for insurance purposes. This method, "Fire Endurance
Protective Envelope Systems for Class 1E Electrical Circuits," specified a circuit
integrity test. The intent of this test was to identify the onset of fire damage
to the cables within the raceway fire barrier test specimen during the fire endurance
test period. The circuit integrity test voltage is 8 to 10 volts DC; therefore
the loss of circuit integrity under these voltage conditions may occur only as
a result of a dead short or open circuit. During fire tests of raceway fire barrier
systems, thermal damage to the cables has been observed. This thermal damage has
led to cable jacket and insulation degradation without the loss of circuit integrity
as monitored using ANI criteria. Since cable voltages used for ANI circuit integrity
tests do not replicate cable operating voltages, loss of cable insulation conditions
can exist during the fire test without a dead short occurring. It is expected
that if the cables were at rated power and current, a fault would propagate. The
use of circuit integrity monitoring during the fire endurance test is not a valid
method for demonstrating that the protected shutdown circuits are capable of performing
their required function during and after the test fire exposure. Therefore, circuit
integrity monitoring is not required to satisfy NRC acceptance criteria for fire
barrier qualification. III. EQUIPMENT QUALIFICATION Comparison of the fire barrier
internal time-temperature profile measured during the fire endurance test to existing
cable performance data, such as data from environmental qualification (EQ) tests,
could be proposed to the staff as a method for demonstrating cable functionality.
EQ testing is typically performed to rigorous conditions, including rated voltage
and current. By correlating the EQ test time-temperature profile to the fire test
time-temperature profile, the EQ test data would provide a viable mechanism to
ensure cable functionality. A large body of EQ test data for many cable types
exists today. The use of EQ data represents a cost-effective approach for addressing
cable functionality for fire tests for those cases where the 163 øC [325 øF] limit
is exceeded. The staff agrees that a comparison of fire test temperature profiles
to existing EQ and Loss of Cooling Accident (LOCA) test results or air oven test
results is an acceptable approach to demonstrate cable functionality provided
the subject analysis incorporates the anticipated temperature rise due to self
heating effects of installed power cables with the fire test results. IV. CABLE
INSULATION TESTS The two principal materials used as cable insulation and cable
jackets by the nuclear industry are thermoplastics and thermosetting polymeric
materials. A thermoplastic material can be softened and resoftened by heating
and reheating. Conversely, thermosetting cable insulation materials cure by chemical
reaction and do not soften when heated. Under excessive heating thermosetting
insulation becomes stiff and brittle. Electrical faults may be caused by softening
and flowing of thermoplastic insulating materials at temperatures as low as 149
øC [300 øF]. Thermosetting electrical conductor insulation materials usually retain
their electrical properties under short- term exposures to temperatures as high
as 260 øC [500 øF]. Insulation resistance (Megger) tests provide indications of
the condition of the cable insulation resistance, whereas the high potential (Hi-Pot)
test provides assurance that the cable has sufficient dielectric strength to withstand
the applied rated voltage. A cable insulation failure usually results from two
breakdown modes: one failure mode is excessive dielectric loss which is due to
low insulation resistance, and the other failure mode is overpotential stress
which is due to loss of dielectric strength of the insulation material. If Megger
tests are not performed at frequent intervals during the fire exposure, indications
of insulation damage in insulation may go undetected. When removed from elevated
temperatures, insulation will reset. Megger tests of insulated cables after the
fire endurance test and after the cable has sufficiently cooled may not detect
degradation in the insulation resistance. Therefore, wet or dry Megger of cables
after a fire exposure does not provide reasonable assurance that the cables would
have functioned as intended during the fire exposure. To provide reasonable assurance
that the cables would have functioned during and after the fire exposure, Megger
tests need to be performed before the fire test, at multiple time intervals during
the fire exposure (i.e, every 20 minutes during the 1-hour fire test and every
hour during the 3-hour fire test) for instrumentation cables only, and immediately
after the fire endurance test to assess the cable insulation resistance levels.
This testing will assure that the cables will maintain the insulation resistance
levels necessary for proper operation of instruments. The Megger tests (pre-fire,
during the fire [if performed], and immediately after the fire test conditions)
should be done conductor-to-conductor for multi-conductor and conductor-to-ground
for all cables. The minimum acceptable insulation resistance (IR) value, using
the test voltage values as shown in the table below, is determined by using the
following expression: IR (Mega-ohms) > {[K+1 Mega-ohm ] * 1000 (ft) } Length (ft)
Where K = 1 Mega-ohm/KV * Operating Voltage (expressed in KV) In addition, to
determine the insulation resistance levels required for nuclear instrumentation
cables, an assessment of the minimum insulation resistance value (e.g., one mega-ohm)
and its potential impact on the functionality of these cables should be evaluated.
An ac or dc high potential (Hi-Pot) test for power cables greater than 1000 volts
(V) should also be performed after the post-fire Megger tests to assess the dielectric
strength. This test provides assurance that the cable will withstand the applied
voltage during and after a fire. The high potential test should be performed for
a 5 minute duration at 60 percent of either 80 V/mil ac or 240 V/mil dc (e.g.,
125 mil conductor insulation thickness x 240 V/mil dc x 0.6 = 18,000 V dc). The
table below summarizes the Megger and Hi-Pot test voltages which, when applied
to power, control and instrumentation cables, would constitute an acceptable cable
functionality test. OPERATING MEGGER TEST HIGH POTENTIAL TYPE VOLTAGE VOLTAGE
TEST VOLTAGE Power > 1000 V ac 2500 V dc 60% x 80 V/mil (ac) 60% x 240 V/mil (dc)
Power < 1000 V ac 1500 V dc* None Instrument < 250 V dc 500 V dc None and < 120
V ac Control * A Megger test voltage of 1000 V dc is acceptable provided a Hi-Pot
test is performed after the Megger test for power cables rated at less than 1000
V ac. The electrical cable functionality tests recommended above are one acceptable
method. Alternate methods to assess degradation of cable functionality will be
evaluated by the staff for acceptability on a case-by-case basis. The above table
summarizing the Megger and Hi-Pot test voltages are "typical" and the applicant
can follow the applicable industry standards and manufacturer's recommendations
for the specific cable application in the performance of the insulation resistance
and Hi-Pot tests. V. AIR OVEN TESTS Air oven tests can be used to evaluate the
functionality of cables for those cable tray or raceway fire barrier test specimens
tested without cables. This testing method consists of exposing insulated wires
and cables at rated voltage to elevated temperatures in a circulating air oven.
The temperature profile for regulating the temperature in the air oven during
this test is the temperature measured by the AWG 8 bare copper conductor during
the fire exposure of those cable tray or raceway test specimen which were tested
without cables. The staff finds the test method described by UL Subject 1724,
"Outline of Investigation for Fire Tests for Electrical Circuit Protective Systems",
Issue Number 2, August 1991, Appendix B, "Qualification Test for Circuit Integrity
of Insulated Electrical Wires and Cables in Electrical Circuit Protection Systems",
with the following modifications, acceptable: 1. During the air oven test the
cables are to be energized at rated voltage. The cables are to be monitored for
conductor-to- conductor faults in multi-conductor cables and conductor-to-ground
faults in all conductors. 2. The cables being evaluated should be subjected to
the Megger and high potential tests, recommended above in Section IV, "Cable Insulation
Tests." 3. The impact force test, which simulates the force of impact imposed
on the raceway by the solid stream test, described in UL 1724, Appendix B, paragraph
B3.16, is not required to be performed. VI. CABLE THERMAL EXPOSURE THRESHOLD The
following analysis, which is based on determining whether a specific insulation
material will maintain electrical integrity and operability within a raceway fire
barrier system during and after an external fire exposure, is an acceptable method
for evaluating cable functionality. In order to determine cable functionality,
it is necessary to consider the operating cable temperatures within the fire barrier
system at the onset of the fire exposure and the thermal exposure threshold (TET)
temperature of the cable. For example, if the TET of a specific thermoplastic
cable insulation (Brand X) is 149 øC [300 øF] and the normal operating temperature
within the fire barrier system is 66 øC [150 øF], then the maximum temperature
rise within the fire barrier system should not exceed 83 øC [150 øF] during exposure
to an external fire of a duration equal to the required fire resistance rating
of the barrier. For this example the TET limit for Brand X cable is 83 øC [150
øF] above the cable operating temperatures within the fire barrier system at the
onset of the external fire exposure. The cable TET limits in conjunction with
a post test visual cable inspection and the Hi-Pot test described above should
readily demonstrate the functionality of the cable circuit during and after a
fire. The normal cable operating temperature can be determined by loading cable
specimens installed within a thermal barrier system in the test configuration
with rated voltage and current. The TET temperature limits for most cable insulation
may be obtained from the manufacturer's published data which is given as the short-circuit
rating limit. With the known TET and normal operating temperature for each thermal
barrier system configuration, the maximum temperature rise limit within a fire
barrier system may then be determined. COMPARISON OF FIRE ENDURANCE TEST CRITERIA
FOR FIRE BARRIER SYSTEMS USED TO SEPARATE SAFE SHUTDOWN FUNCTIONS WITHIN THE SAME
FIRE AREA GL 86-10, SUPP. 1GL 86-10RATIONALE FOR CLARIFICATIONTemperature,
as measured on the external surface of the Raceway, should not exceed 163 øC [325
øF] (Note 1). This temperature is determined by averaging temperature readings
of similar series of thermocouple (e.g., cable tray side rail) (Note 2). Barrier
Condition - Fire barrier should remain intact. No visible signs of component,
raceway or cables after fire and hose stream test. Hose Stream Test - solid stream
test as specified in NFPA 251 on second test specimen after being subjected to
a fire exposure of 1/2 duration (Note 4) or a fog stream after the full fire exposure.
Temperature, as measured on the unexposed side of the fire barrier material, should
not exceed 163 øC [325 øF]. Barrier Condition - The barrier should have withstood
the fire and hose stream test without the passage of flame or hot gasses hot enough
to ignite cotton waste. Hose Stream Test - solid stream test as specified in NFPA
251. Temperature - Difficult to measure a uniform temperature on the fire barrier
material surface. Raceway temps provide good indication of internal temp-rise
and potential barrier failure locations during the test. Barrier Condition - Cotton
waste has not been used in raceway fire barrier testing as an indicator of barrier
failure. Visual inspection process provides a better indication of barrier condition
after the fire and hose stream test. Hose Stream Test - To reflect alternative
methods found acceptable (Note 3). The use of a fog nozzle for the hose stream
at the end of a full duration of the fire test provides a good method for testing
erosion and cooling effects. GL 86-10, SUPP. 1GL 86-10RATIONALE FOR CLARIFICATION
Cable condition - When cables are included in the test specimen, post-fire condition
must be visually inspected. Cables should show no signs of degraded conditions
resulting from the thermal affects of the fire exposure.Cable condition - No
consideration given to determining the material condition of the cable. Cable
condition - The objective of these fire barriers is to assure that thermal damage
to protected safe shutdown cables or components does not occur. GUIDANCE FOR ENGINEERING
EVALUATIONS JUSTIFYING DEVIATIONS FROM THE FIRE BARRIER ACCEPTANCE CRITERIA Functionality
should be demonstrated if any of the preceding criteria are exceeded (Note 5).
Methods when cables are excluded from test specimen: Comparison of internal temp.
profiles to EQ and LOCA test data. Air oven test of cables at rated voltage with
Megger and Hi-Pot tests (Note 6) Method when cables are in test specimen include
megger and Hi-Pot testing (Note 7) Demonstration of functionality should also
consider operating temperature of the cables inside the fire barrier at the onset
of the fire exposure. Functionality - No guidance provided. Up to licensees to
demonstrate by engineering analysis. Analysis kept on file for NRC review. Engineering
analysis generally based on internal temperature below the ignition temperature.
No consideration given cable operating temperatures within the barrier at the
onset of the fire exposure. Functionality is considered to be a deviation from
the acceptance criteria and must be justified on a case-by-case basis which includes
an assessment of cable jacket material. Note 1: The 163 øC [325 øF] temperature
condition was established by allowing the internal temperature on the raceway
surface to rise a maximum of 139 øC [250 øF] above the initial temperature of
the test specimen (assumed to be 24 øC [75 øF]). Note 2: NFPA 251/ASTM-E119 allows
the temperature condition to be determined by averaging the thermocouple readings.
The conditions of acceptance are also placed on the temperature conditions measured
by a single thermocouple. Under these conditions of acceptance, if any single
thermocouple exceeds 30 percent above the maximum allowable temperature rise (i.e.,
max. allowable 139 øC + 42 øC = 181 øC [250 øF + 75 øF = 325 øF]) the test is
considered to have exceeded the criteria temperature limit. Note 3: SRP 9.5.1
recognizes the use of a fog stream as an alternative hose stream testing method
for qualifying fire barrier penetration seals. Note 4: This hose stream test method
provides assurance that the cable tray or raceway fire barrier system has sufficient
structural integrity to resist minor fire related barrier breaches caused by falling
objects. Note 5: A fire barrier system that does not meet the acceptance criteria
is not considered a rated fire barrier. For those conditions (e.g., high raceway
temperature, barrier openings, water projection, cable damage) which deviate from
the acceptance criteria, an engineering analysis which clearly demonstrates the
functionality of the protected components or cables should be submitted to the
staff for review. The purpose of the recommended functionality tests is to justify
observed deviations in fire barrier performance. Engineering analyses justifying
these deviations should not rely substantially upon the equipment (e.g., cable)
qualification as the basis for acceptance. Deviations will be evaluated by the
staff on a case-by-case basis. Note 6: For fire barrier systems tested without
cables, plant-specific cable types should be subjected to air oven tests when
the fire barrier temperature rise criteria are exceeded. These cables will be
exposed to a temperature profile as determined by the internal raceway thermocouples
during the fire test. Cables will be tested at rated voltage. Megger and Hi-Pot
testing should be performed in a consistent manner to those tests performed for
cables included in a fire barrier test specimen and subjected to the fire endurance
test. Note 7: Megger tests of cables included in the fire test specimen should
be performed before, during (instrumentation cables only) and immediately after
the fire exposure and subjecting power cables which have voltage ratings > 1000
volts ac to a Hi-Pot test (60 percent) immediately after the fire exposure.